Florida Blower Door Test Requirements, Explained
Florida requires an air leak test on new homes. In the area we serve, the limit is 7 air changes per hour at 50 pascals.
Get a Quote
When it is required
When a test is required
Florida requires the test on newly built homes. The rule is in the Florida Building Code, Energy Conservation.
The house is ready once the outside walls and ceiling are closed up, with every window, door, pipe, wire and vent in place. The rest of the house does not need to be finished.

The limit
The 7 ACH50 limit
Florida's energy code limits a new house to 7 air changes per hour at test pressure.
The test pressure is 50 pascals, so the result is written ACH50. A lower number means a tighter house.

Test day
How the house is set up on test day
A fan set in an outside doorway holds the house at the test pressure while the air leakage is measured.
Outside windows and doors are closed, inside doors are open, the heating and cooling is off, and the supply and return registers are open.

The code
Where the Florida blower door test requirements come from
The rule is in the Florida Building Code, Energy Conservation, at section R402.4.1.2 of the 2023 edition. It sets the limit for Climate Zones 1 and 2, tested at 0.2 inches of water, the same pressure as 50 pascals. Every county we serve is in Climate Zone 2.
The math
How the result is worked out: CFM50 and ACH50
The test gives two numbers. CFM50 is how many cubic feet of air per minute the fan moves to hold the house at 50 pascals. That is the raw leak rate.
ACH50 takes the CFM50, multiplies it by 60 minutes, and divides by the volume of air inside the house. That turns the leak rate into air changes per hour, so a small house and a large house are judged by the same limit.
For example, a house with 2,000 square feet of floor and 9 foot ceilings holds 18,000 cubic feet of air. At 7 ACH50, that house could leak up to 2,100 CFM50.
The report
The report the building official gets
The code asks for a written report of the result, signed by the person who ran the test, for the code official. Every blower door test we run ends with a signed report of the result, ready for the building official.
Additions
Additions and alterations
An addition or alteration that makes up less than 85 percent of the building shell does not need the test. Your building official decides whether that applies to your project.
Next steps
Getting ready, and what happens if the house does not pass
Our test preparation page covers getting a house ready for the test. If a house tests over the limit, the leaks are sealed and the house is tested again. See failed blower door test.
Should the drain traps have water in them?
The drain traps should have water in them. A dry trap is an open path to the plumbing vent on the roof, so a little water goes down each sink, tub and shower drain before the test.
Can the crew keep working during the test?
The crew can keep working inside during the test. They just keep the outside doors and windows shut and leave other fans off while the test fan runs.
Do the bath fans and range hood need to be installed?
The bath fans and range hood need to be installed. Each one makes an opening through the walls or roof, and the test counts the openings that exist on test day.
Should the fresh air or ventilation system be off?
The fresh air or ventilation system should be off, with its damper closed, so it does not move air through the house during the test.
Get a Quote
Book your blower door test
Send the form and we will reach out to set up your test. Prefer to talk? Give us a call.
Call (850) 819-6031Serving the Florida Panhandle since 2017
Get a Quote
Keep reading


